Flame/spark detector UV2/PSD2

Search

Discover our collection of flame and spark detectors:

UV2 flame detector

The UV2 flame detector is a flame detector based on a UV bulb sensor. It detects light in the UV-C range between 185 and 260 nm and it is therefore insensitive to sunlight and common artificial light sources. The UV2 flame detector is well protected against influences of:

  • Direct or reflected sunlight.
  • Artificial lights such as fluorescent tube or glazed protected halogen lamps.
  • Chopped or moving hot body radiation from machines or exhausts.

Electrical welding arcs and flames of any kind (i.e. gas burners) and other source which are emitting in the 185 to 260 nm (i.e. naked halogen lamp) will be detected.

In order to avoid false alarms due to background radiation in the vicinity of the detector, a configurable (via DIPSwitches) number of detection pulses are requested to activate the alarm output. Vision impairment is detected via an IR light. Extensive dirt on the window will activate the failure output. The supply voltage of the UV bulb is also monitored. The UV2 detector will be used for open fires such as class B fires and for all kind of fire where the flames appear first.

Technical information UV2 flame detector

  • Supply voltage: 12 to 30 V DC
  • Operating temperature: 0° C to +70 °C
  • Storage temperature: -20 °C to +80 °C
  • Housing: aluminium box blue RAL5012
  • Field of view: > 80° horizontal x 80° vertical
  • Overall dimensions: 140 x 90 x 70 mm
  • Response time (dependent on the configured number of detection pulses): <50 ms
  • Current draw (dependent on the voltage supply):
    • standby ca. 25 mA @24V DC
    • alarm ca. 35 mA @24V DC
  • Outputs (values maybe changed on request by our technical department):
    • Standby: 3K9
    • Alarm: 3K9 // 680 Ohm
  • or (factory set):
    • 1 NO Alarm potential free contact
    • 1 NC Fault potential free contact
  • Both of the contacts have latched or pulsed activation configurable via DIP-Switches
  • Internal indication (visible when facing the detector):
    • 1 yellow LED
      • Blinking: OK
      • On: failure
      • Off: lack of power supply
    • 1 red LED
      • Of : normal
      • On : Alarm
  • Wiring via internal 8-poles screw terminal
  • 1 or 2 x M12 cable-glands
  • Cable requirement:
    • Flexible and shielded 4 x 0.5 mm2 cable
    • 6 mm2 earthing wire
  • Reset by switching-off the voltage supply
  • Protection: IP65
  • Conformity: Class 1 EN54-10
  • Certification: II 3 D ATEX Z22
  • Weight: approximate 600 g
  • Available accessories:
    • Airshield head: in order to avoid accumulation of dust.
    • FOV-reduction head: it reduces the FOV of the detector to ca. 25°.

Conditions of use UV2 flame detector

  • Correct use:
    • Indoor flame detection
    • Open fire
    • Cold or invisible flames such as Hydrogen, Hydride, Ammonia and other non-organic propellant.
    • Fires of metals
    • Other fires:
      • Gasoline
      • Diesel
      • Kerosene
      • Alcohol
      • LNG / LPG
      • Solvents
      • Glues
      • N-Heptane
  • Special cautions:
    • Halogen surrounding lighting
    • Exposure to UV radiance (arc from welding works, sparks...)
    • Dusty or smoky environment
    • Oil or grease deposit may affect the sensitivity of the detector

Applications UV2 flame detector

  • Flame detection within volumes
  • Electrostatic powder spraybooth
  • Gas turbines rooms
  • Chemical storage
  • Gas & solvent storage
  • Laboratories
  • Tooling machines

Ordering information UV2 flame detector

  • 76.01.00001: UV2-1 detector PAGG outputs (end of line)
  • 76.01.00002: UV2-2 detector PAGG outputs (intermediate)
  • 76.01.00003: UV2-F detector with free potential contacts
  • 70.99.00000: standard coupling ring
  • 71.99.00000: airshield coupling ring
  • 71.99.00008: swivel mount
  • 70.99.00008: FOV-reduction head #1 for UV2
  • 70.99.00009: FOV-reduction head #2 for UV2
  • 70.99.00001: standard ring mount
  • 70.99.00003: 45°-ring mount

 

PSD2 spark detector

The PSD2 is a spark detector in the infrared IR-A range. It is intended forfire protection systems of industrial process (pneumatic conveying ducts for example). The PSD2 detector reacts to all IR sources between 780 and 1100 nm. It must be installed in total darkness environment. The PSD2 detector is equipped with a test input in order to check the functioning of the detection cell.  Outputs are available for compatibility with PAGG control panels or with free potential contacts.

Technical information PSD2 spark detector

  • Supply voltage: 12 to 30 V DC
  • Operating temperature: 0°C to +80 °C
  • Storage temperature: -20°C to +80 °C
  • Housing: aluminium
  • Field of vision: 95°
  • Dimensions:
    • Housing 125 x 80 x 55 mm
    • Head Ø 16 mm x 40 mm
  • Capture time: ≤1 ms
  • Response time: ≤1,2 ms
  • Current requirement: max. 40 mA @ 24V DC
  • Indication:
    • Green LED: standby condition
    • Red LED: alarm
  • Outputs (factory set): PAGG panels compatible (standby : 3K9 and alarm : 3K9 // 680 Ohm) Free contact: Alarm = NO Fault = NC
  • Output mode: Pulsed (10 ms) or latched (selection by jumper)
  • Wiring via internal 10-poles screw terminal
  • Cable requirement:
    • min. 4 x 0.5 mm2 flexible and shielded cable
    • 6 mm2 earthing wire
  • Reset by switching off the voltage supply
  • Sensitivity: adjustable via 4 DIP-switches
  • Protection: IP65
  • Conformity:
  • Weight: approximate 1 kg
  • Option: integrated spark counter

Applications PSD2 spark detector

  • Process monitoring
  • Wood processing industry
  • Protection dust cleaning filters
  • Drier monitoring

 

Interested?